CC1800

Designed for Booster applications

The newly designed CC1800 Axial Fans are designed specifically for booster applications. Available as single or twin stage configurations with flow rates up to 105 m³/s and pressures up to 4 kPa per stage. The CC1800 is a variable pitch design capable of a wide range of duties and applications.

CC1800 Product Guide
Product specifications
Description Fan Speed Number of Blades Blade Angles Motor Size
CC1800Mk1 Axial Booster Fan 1495RPM 12 42-57 Degrees 160kW to 400kW
1495RPM 6 42-62 Degrees 110kW to 350kW
990RPM 12 62-72 Degrees 150kW to 220kW
Fan specifications
Fan Specification Description
Fan Design Co-Rotating
Fan Stages Single or Twin Stage Configurations
Motor Power 110kW to 300kW
Internal Diameter 1800mm
Casing Thickness 8mm with 20mm Machined Impeller Track
Casing Finish Galvanising
Flange OD 1986mm
Hole PCD 1900mm
Number of Holes 24
Hole Size 22mm
Hole Orientation Offset from Top Dead Center
Lifting Mechanism Full Length Lifting Bar with 40mm Holes
Serial Numbering Laser Cut Stainless Steel Plates
Airflow And Rotor Direction PolyCarbonate Arrows on Casings
Impeller specifications
Impeller Specification Description
Blade Material AC601 Aluminium Alloy or SG Iron
Hub Material SG Iron Cast Hub
Design High Efficiency Variable Pitch Castings
Casting Method Sand and Gravity Feed Casting
Finish Bare Metal, Epoxy Coatings on Request
Motor specifications
Motor Specification Description
Windings H Class Custom Specfication
Insulation Double H Class Insulation
Efficiency >94%
Voltage 415v, 525v, 690v and 1000v
Frequency 50hz / 60hz (6P Opertation Only @ 60Hz)
Poles 4P, 6P
Speed 990RPM / 1475RPM
Frame D280 / D350
Mounting Foot Mounting
Leads 1m Extended From Casing
Terminal Box External on Fan Casing
Terminal Box Protection Steel Guard around Box

Key points

  • Co-Rotating Design
  • Booster Fan Applications
  • Variable Pitch Blade Adjustment
  • Machined Impeller Track
  • Modular Single or Twin Stage Configurations
  • Flow Rates from 35 m³/s to 105 m³/s
  • Pressures from 500 Pa to 4000 Pa per Stage